• Feed RSS

Pages

Selasa, 26 Oktober 2010

Electrical Conduit

Bookmark and Share
An electrical conduit is an electrical piping system used for protection and routing of electrical wiring. Electrical conduit may be made of metal, plastic, fiber, or fired clay. Flexible conduit is available for special purposes.

Conduit is generally installed by electricians at the site of installation of electrical equipment. Its use, form, and installation details are often specified by wiring regulations, such as the U.S. NEC or other national or local code. The term "conduit" is commonly used by electricians to describe any system that contains electrical conductors, but the term has a more restrictive definition when used in wiring regulations.

Early electric lighting installations made use of existing gas pipe to gas light fixtures (converted to electric lamps). Since this technique provided very good protection for interior wiring, it was extended to all types of interior wiring and by the early 20th century purpose-built couplings and fittings were manufactured for electrical use.

Comparison with other wiring methods


Electrical conduit provides very good protection to enclosed conductors from impact, moisture, and chemical vapors. Varying numbers, sizes, and types of conductors can be pulled into a conduit, which simplifies design and construction compared to multiple runs of cables or the expense of customised composite cable. Wiring systems in buildings are subject to frequent alterations. Frequent wiring changes are made simpler and safer through the use of electrical conduit, as existing conductors can be withdrawn and new conductors installed, with little disruption along the path of the conduit. A conduit system can be made waterproof or submersible. Metal conduit can be used to shield sensitive circuits from electromagnetic interference, and also can prevent emission of such interference from enclosed power cables.
When installed with proper sealing fittings, a conduit will not permit the flow of flammable gases and vapors, which provides protection from fire and explosion hazard in areas handling volatile substances.

Some types of conduit are approved for direct encasement in concrete. This is commonly used in commercial buildings to allow electrical and communication outlets to be installed in the middle of large open areas. For example, retail display cases and open-office areas use floor-mounted conduit boxes to connect power and communications cables.

Both metal and plastic conduit can be bent at the job site to allow a neat installation without excessive numbers of manufactured fittings. This is particularly advantageous when following irregular or curved building profiles.

The cost of conduit installation is higher than other wiring methods due to the cost of materials and labor. In applications such as residential construction, the high degree of physical damage protection is not required so the expense of conduit is not warranted. Conductors installed within conduit cannot dissipate heat as readily as those installed in open wiring, so the current capacity of each conductor must be reduced if many are installed in one conduit. It is impractical, and prohibited by wiring regulations, to have more than 360 degrees of total bends in a run of conduit, so special outlet fittings must be provided to allow conductors to be installed without damage in such runs. While metal conduit can be used as a grounding conductor, the circuit length is limited. A long run of conduit as grounding conductor will not allow proper operation of overcurrent devices on a fault, for example.

Types of conduit

Conduit systems are classified by the wall thickness, mechanical stiffness, and material used to make the tubing.

Rigid Metal Conduit (RMC)

Rigid Metal Conduit (RMC) is a thick threaded tubing, usually made of coated steel, stainless steel or aluminum.

Rigid Nonmetallic Conduit (RNC)

Rigid Nonmetallic Conduit (RNC) is a non-metallic unthreaded tubing.

Galvanized rigid conduit (GRC)

Galvanized rigid conduit (GRC) is galvanized steel tubing, with a tubing wall that is thick enough to allow it to be threaded. Its common applications are in commercial and industrial construction.

Electrical metallic tubing (EMT)

Electrical metallic tubing (EMT), sometimes called thin-wall, is commonly used instead of galvanized rigid conduit (GRC), as it is less costly and lighter than GRC. EMT itself may not be threaded, but can be used with threaded fittings that clamp to it. Lengths of conduit are connected to each other and to equipment with clamp-type fittings. Like GRC, EMT is more common in commercial and industrial buildings than in residential applications. EMT is generally made of coated steel, though it may be aluminum.

Electrical Nonmetallic Tubing (ENT)

Electrical Nonmetallic Tubing (ENT) is a thin-walled corrugated tubing that is moisture-resistant and flame retardant. It is pliable such that it can be bent by hand and is often flexible although the fittings are not. It is not threaded due to its corrugated shape although the fittings might be.

Flexible Metallic Conduit (FMC)

Flexible Metallic Conduit (FMC) is made through the coiling of a self-interlocked ribbed strip of aluminum or steel, forming a hollow tube through which wires can be pulled. FMC is used primarily in dry areas where it would be impractical to install EMT or other non-flexible conduit, yet where metallic strength to protect conductors is still required. The flexible tubing does not maintain any permanent bend.

Cutting FMC requires a specialized hand tool with a rotary abrasive disc to creates a small incision into the ribbing so that a twisting motion separates the segments. The disc cuts deep enough to sever the armor coil but not so deep that it could damage the inside conductors.

Short segments of FMC called whips are often used as circuit "pigtails" between fixtures and a junction box, especially in suspended ceilings. Whip assemblies save a great deal of repetitive labor when installations require several pigtails for several fixtures.

Flexible metal conduit coated with a UV-resistant polymer is liquid-tight when installed with appropriate glandular fittings containing liquid-tight features such as O-rings.

Wiring regulations vary; in locales following the U.S. National Electric Code (NEC), flexible metallic conduit may serve as an equipment-grounding conductor. Other areas may require a bonding wire for equipment grounding. The bonding wire in direct contact with the interior of the conduit creates a lower resistance grounding conductor than the conduit alone.

Liquidtight Flexible Metal Conduit (LFMC)

Liquidtight Flexible Metal Conduit (LFMC) is a metallic flexible conduit covered by a waterproof plastic coating. The interior is similar to FMC.

Flexible Metallic Tubing (FMT)

Flexible Metallic Tubing (FMT) is not the same as Flexible Metallic Conduit (FMC) aka "greenfield" or "flex" which is National Electrical Code (NEC) Art 348. FMT is a raceway, but not a conduit and is a separate NEC Article - 360. It only comes in 1/2" & 3/4" trade sizes whereas FMC is sized 1/2" ~ 4" trade sizes. NEC 360.2 describes it as: "A raceway that is circular in cross section, flexible, metallic and liquidtight without a nonmetallic jacket."

Liquidtight Flexible Nonmetallic Conduit (LFNC)

Liquidtight Flexible Nonmetallic Conduit (LNFC) refers to several types of flame-resistant non-metallic tubing. Interior surfaces may be smooth or corrugated. There may be integral reinforcement within the conduit wall. It is also known as FNMC.

Aluminum conduit

Aluminum conduit, similar to galvanized steel conduit, is a rigid conduit, generally used in commercial and industrial applications, where a higher resistance to corrosion is needed. Such locations would include food processing plants, where large amounts of water and cleaning chemicals would make galvanized conduit unsuitable. Aluminum cannot be directly embedded in concrete, since the metal reacts with the alkalis in cement. The conduit may be coated to prevent corrosion by incidental contact with concrete. The extra cost of aluminum is somewhat offset by the lower labor cost to install, since a length of aluminum conduit will have about one-third the weight of an equally-sized rigid steel conduit.

Intermediate metal conduit (IMC)

Intermediate Metal Conduit (IMC) is a steel tubing heavier than EMT but lighter than RMC. It may be threaded.

PVC conduit

PVC conduit is the lightest in weight compared to other conduit materials, and usually lower in cost than other forms of conduit. In North American electrical practice, it is available in three different wall thicknesses, with the thin-wall variety only suitable for embedded use in concrete, and heavier grades suitable for direct burial and exposed work. The various fittings made for metal conduit are also made for PVC. The plastic material resists moisture and many corrosive substances, but since the tubing is non-conductive an extra bonding (grounding) conductor must be pulled into each conduit. PVC conduit may be heated and bent in the field. Joints to fittings are made with slip-on solvent-welded connections,which set up rapidly after assembly and attain full strength in about one day. Since slip-fit sections do not need to be rotated during assembly, the special union fittings used with threaded conduit (Ericson) are not required. Since PVC conduit has a higher thermal coefficient of expansion than other types, it must be mounted so as to allow for expansion and contraction of each run. Care should be taken when installing PVC underground in multiple or parallel run configurations due to mutual heating effect of cable

Other metal conduits

In extreme corrosion environments where plastic coating of the tubing is insufficient, conduits may be made from stainless steel, bronze or brass.

Underground conduit

Large diameter (more than 2 inch/50 mm) conduit may be installed underground between buildings to allow installation of power and communication cables. An assembly of these conduits, often called a duct bank, may either be directly buried in earth or encased in concrete. A duct bank will allow replacement of damaged cables between buildings or additional power and communications circuits to be added, without the expense of excavation of a trench. While metal conduit is occasionally used for burial, usually PVC, polyethylene or polystyrene plastics are now used due to lower cost. Formerly, compressed asbestos fiber mixed with cement was used for some underground installations. Telephone and communications circuits were installed in fired-clay conduit.

Sumber: www.wikipedia.org


Post Terkait

1 komentar:

  1. Sounds Pretty,
    Use best quality flexible electrical conduit for your wire fitting at your home or office. Thanks for sharing this amazing post.

    BalasHapus